Voltage Drop Calculator
Check how much voltage you lose over a run. Uses the common K-factor method.
Estimate only. This is a quick check. Wire sizing has to meet the current code book and your AHJ. Ampacity, temperature, and fill rules are separate checks.
Result
Fill in your numbers and hit Calculate.
Did that help?
Get one jobsite shortcut a week. Free tools, AI prompts, and lead skills for the field. Get The Tailgate
How the math works
Single phase: VD = 2 x K x I x L / CM
Three phase: VD = 1.732 x K x I x L / CM
K = 12.9 copper, 21.2 aluminum (ohm-cmil per ft, approx.)
L = one-way length in feet, CM = circular mils of the wire
Percent drop = VD / source volts x 100Circular mil sizes are the standard AWG and kcmil values. A common design target is about 3% on a branch circuit and 5% total, which the NEC mentions in informational notes. Your specs or AHJ may say different.